DATI PRESTAZIONALI
            NSMI - A/E
            Taglia                       1251  1601  1801  2352  2652  2802  3202  3402  3802  4102  4402  4802  5202  5702  6102
            Prestazioni in raffreddamento 12 °C / 7 °C (1)

            Potenza frigorifera      kW  285,6  382,0  464,0  519,1  605,4  659,4  725,2  802,4  842,6  948,0  1008,8  1110,4  1204,3  1253,0  1342,6
            Potenza assorbita        kW  91,3  120,2  149,5  167,1  194,3  212,3  232,7  257,5  269,9  304,8  324,7  356,2  397,4  415,9  454,6
            Corrente assorbita totale a freddo  A  155,0  200,0  245,0  293,0  337,0  360,0  393,0  431,0  443,0  517,0  547,0  619,0  665,0  728,0  761,0
            EER                      W/W  3,13  3,18  3,10  3,11  3,12  3,11  3,12  3,12  3,12  3,11  3,11  3,12  3,03  3,01  2,95
            Portata acqua utenza     l/h  49130  65700  79773  89247  104092 113376 124682 137945 144852 162983 173442 190903 207040 215409 230815
            Perdita di carico lato utenza  kPa  45  15  21  18  25  28  33  27  30  39  45  38  44   49  55
            (1)  Dati EN 14511:2022; Acqua scambiatore lato utenza 12 °C / 7 °C; Aria esterna 35 °C
              INDICI ENERGETICI (REG. 2016/2281 UE)
            Taglia                         1251  1601  1801  2352  2652  2802  3202  3402  3802  4102  4402  4802  5202  5702  6102
            SEER - 12/7 (EN14825: 2018) con ventilatori standard (1)
            SEER                  A,E  W/W  4,75  4,82  4,78  4,90  4,92  4,90  4,91  4,93  4,93  4,90  4,88  4,90  4,85  4,70  4,69
            Effi  cienza stagionale  A,E  %  186,8% 189,7% 188,0% 193,1% 193,9% 193,0% 193,3% 194,2% 194,3% 192,8% 192,2% 192,9% 191,0% 185,1% 184,7%
            SEER - 12/7 (EN14825: 2018) con ventilatori inverter (1)
            SEER                  A,E  W/W  4,95  5,04  5,00  5,01  5,03  5,01  5,02  5,04  5,04  5,00  4,99  5,00  4,96  4,81  4,80
            Effi  cienza stagionale  A,E  %  194,9% 198,4% 196,8% 197,3% 198,1% 197,2% 197,6% 198,5% 198,5% 197,1% 196,4% 197,1% 195,3% 189,2% 188,8%
            SEPR - (EN 14825: 2018) Alta temperatura con ventilatori standard (2)
            SEPR                  A,E  W/W  5,70  5,62  5,59  6,56  6,43  6,42  6,77  6,94  7,21  6,96  7,47  6,88  7,21  6,69  7,01
            SEPR - (EN 14825: 2018) Alta temperatura con ventilatori inverter (2)
            SEPR                  A,E  W/W  5,70  5,62  5,59  6,56  6,43  6,42  6,77  6,94  7,21  6,96  7,47  6,88  7,21  6,69  7,01
            (1)  Calcolo eseguito con portata d’acqua FISSA e temperatura d’uscita VARIABILE.
            (2)  Calcolo eseguito con portata d’acqua FISSA.
            DATI ELETTRICI
            Taglia                     1251  1601  1801  2352  2652  2802  3202  3402  3802  4102  4402  4802  5202  5702  6102
            Dati elettrici
            Corrente massima (FLA)  A,E  A  251,3  291,3  377,7  442,0  473,0  519,4  519,4  567,4  653,8  708,1  753,5  874,8  917,2  1002,2  1036,2
            Corrente di spunto (LRA)  A,E  A  51,3  51,3  57,7  571,7  605,0  651,4  651,4  775,4  861,8  989,1  1059,4  1180,2  1335,2  1420,2  1532,2

            DATI TECNICI GENERALI
            Taglia                         1251  1601  1801  2352  2652  2802  3202  3402  3802  4102  4402  4802  5202  5702  6102
            Compressore
            Tipo                  A,E  tipo                               Vite
            Regolazione compressore  A,E  Tipo  I  I  I  1+I  1+I  1+I  1+I  1+I  1+I  1+I  1+I  1+I  1+I  1+I  1+I
            Numero                A,E  n°   1   1    1   2    2   2   2    2   2    2   2   2    2   2    2
            Circuiti              A,E  n°   1   1    1   2    2   2   2    2   2    2   2   2    2   2    2
            Refrigerante          A,E  tipo                               R134a
            Carica refrigerante (1)  A,E  kg  28,0  28,0  30,0  81,0  92,0  110,0  114,0  107,0  131,0  146,0  163,0  183,0  183,0  195,0  195,0
            Scambiatore lato utenza
            Tipo                  A,E  tipo                             Fascio tubiero
            Numero                A,E  n°   1   1    1   1    1   1   1    1   1    1   1   1    1   1    1
            Attacchi idraulici
            Attacchi (in/out)     A,E  Tipo                             Giunti scanalati
            Diametro (in/out)     A,E   Ø   5”  6”   6”  6”  6”   6”  6”   8”  8”  8”   8”  10”  10”  10”  10”
            (1)  La carica riportata in tabella è un valore stimato e preliminare. Il valore finale della carica di refrigerante è riportato nella targhetta tecnica dell’unità. Per maggiori informazioni contattare sede.

            Ventilatori
            Taglia                         1251  1601  1801  2352  2652  2802  3202  3402  3802  4102  4402  4802  5202  5702  6102
            Ventilatori: °
            Ventilatore
            Tipo                  A,E  tipo                               Assiale
            Motore ventilatore    A,E  tipo                          Asincrono con taglio di fase
            Numero                A,E  n°   8   8    10  10  12   14  14   14  16  18   20  22   22  22  22
            Portata aria          A,E  m³/h  128000 128000 160000 160000 192000 224000 224000 224000 256000 288000 320000 396000 396000 396000 396000
            Dati sonori
            Taglia                         1251  1601  1801  2352  2652  2802  3202  3402  3802  4102  4402  4802  5202  5702  6102
            Dati sonori calcolati in funzionamento a freddo (1)
                                  A    dB(A)  97,2  98,6  98,6  98,6  98,8  99,9  99,9  100,3  100,3  100,4  101,0  102,9  103,2  102,9  103,2
            Livello di potenza sonora
                                  E    dB(A)  92,9  95,8  95,9  94,7  95,1  96,1  96,1  97,3  97,4  97,7  98,0  99,9  99,9  99,9  99,9
                                  A    dB(A)  64,8  66,2  66,1  66,1  66,2  67,1  67,1  67,5  67,5  67,4  67,9  69,7  69,9  69,7  69,9
            Livello di pressione sonora (10 m)
                                  E    dB(A)  60,6  63,4  63,4  62,1  62,5  63,3  63,3  64,6  64,5  64,7  64,8  66,7  66,7  66,7  66,7
            (1)  Potenza sonora: calcolata sulla base di misure effettuate in accordo con la normativa UNI EN ISO 9614-2, nel rispetto di quanto richiesto dalla certificazione Eurovent.; Pressione sonora misurata in campo libero, a 10 m di distanza dalla


             superficie esterna dell’unità (in accordo con la UNI EN ISO 3744).



       538                                             www.aermec.com                     NSMI-1251-5202-CO_I_UN50_04