Page 335 - AERMEC - CATALOGO PRODOTTI 2023 - DELLAFIORE
P. 335

DATI PRESTAZIONALI
               DATI TECNICI EUROVENT EN 14511:2013
                                            HMI040  HMI060  HMI080  HMI100  HMI100T  HMI120  HMI120T  HMI140  HMI140T  HMI160  HMI160T
            Prestazioni in raffreddamento 12 °C / 7 °C - EN 14511:2013 (1)


            Potenza frigorifera        kW    3,00  4,00  5,00  7,80  7,80  9,50  9,50  12,00  12,00  13,00  13,00
            Potenza assorbita          kW    0,94  1,29  1,61  2,48  2,64  3,20  3,11  4,14  4,38  4,96  4,91
            Corrente assorbita         A     4,3   5,9   7,7   11,4  4,0   14,7  4,7  19,0   6,7  22,7  7,5
            EER                       W/W    3,19  3,10  3,11  3,15  2,95  2,97  3,05  2,90  2,74  2,62  2,65
            Portata acqua              l/h   516   672   860   1320  1270  1650  1665  2080  2065  2270  2231
            Prevalenza utile           kPa   75,0  74,0  74,0  71,0  71,0  65,0  64,0  51,0  51,0  45,0  46,0
            Prestazioni  in riscaldamento 40 °C / 45 °C - EN 14511:2013 (2)
            Potenza termica            kW    4,00  6,00  7,50  10,00  10,00  12,00  12,00  14,00  14,00  15,50  15,50
            Potenza assorbita          kW    1,00  1,58  2,00  2,70  2,70  3,48  3,48  4,18  4,18  4,70  4,70
            Corrente assorbita         A     4,6   7,2   9,2   12,4  4,1   15,9  5,3  19,1   6,4  21,5  7,1
            COP                       W/W    4,00  3,80  3,75  3,70  3,70  3,45  3,45  3,35  3,35  3,30  3,30
            Portata acqua              l/h   690   977   1240  1700  1710  2050  2040  2500  2474  2700  2734
            Prevalenza utile           kPa   74,0  73,0  72,0  63,0  63,0  52,0  52,0  37,0  38,0  30,0  29,0
            (1)  Dati EN 14511:2013; Acqua scambiatore lato utenza 12 °C / 7 °C; Aria esterna 35 °C
                                                                                                                      ARIA-ACQUA
            (2)  Dati EN 14511:2013; Acqua scambiatore lato utenza 40 °C / 45 °C; Aria esterna 7 °C b.s. / 6 °C b.u.
                                            HMI040  HMI060  HMI080  HMI100  HMI100T  HMI120  HMI120T  HMI140  HMI140T  HMI160  HMI160T
            Prestazioni in raffreddamento 23 °C / 18 °C - EN 14511:2013 (1)

            Potenza frigorifera        kW    3,80  5,80  6,80  8,80  8,80  11,00  11,00  12,50  12,50  14,50  14,50
            Potenza assorbita          kW    0,82  1,32  1,55  1,96  1,96  2,56  2,56  3,05  3,05  3,82  3,82
            Corrente assorbita         A     3,8   6,0   7,1   9,0   3,0   11,7  3,9  14,0   4,6  17,5  5,8
            EER                       W/W    4,63  4,39  4,39  4,49  4,49  4,30  4,30  4,10  4,10  3,80  3,80
            Portata acqua              l/h   660   981   1220  1510  1500  1926  1900  2238  2200  2640  2570
            Prevalenza utile           kPa   74,0  73,0  72,0  69,0  69,0  56,0  57,0  46,0  47,0  32,0  34,0

            Prestazioni in riscaldamento 30 °C / 35 °C - EN 14511:2013 (2)
            Potenza termica            kW    4,00  6,00  7,50  10,00  10,00  12,00  12,00  14,00  14,00  15,50  15,50
            Potenza assorbita          kW    0,79  1,20  1,63  2,17  2,17  2,64  2,64  3,22  3,22  3,60  3,60
            Corrente assorbita         A     3,6   5,5   7,5   9,9   3,3   12,1  4,0  14,7   4,9  16,5  5,5
            COP                       W/W    5,10  5,00  4,60  4,61  4,61  4,55  4,55  4,35  4,35  4,31  4,31
            Portata acqua              l/h   690   1030  1247  1736  1720  2137  2100  2524  2400  2703  2626
            Prevalenza utile           kPa   74,0  73,0  72,0  62,0  62,0  49,0  50,0  36,0  40,0  30,0  32,0
            (1)  Dati EN 14511:2013; Acqua scambiatore lato utenza 23 °C / 18 °C; Aria esterna 35 °C
            (2)  Dati EN 14511:2013; Acqua scambiatore lato utenza 30 °C / 35 °C; Aria esterna 7 °C b.s. / 6 °C b.u.
               DATI TECNICI EUROVENT EN 14511:2018
                                            HMI040  HMI060  HMI080  HMI100  HMI100T  HMI120  HMI120T  HMI140  HMI140T  HMI160  HMI160T
            Prestazioni in raffreddamento 12 °C / 7 °C (1)

            Potenza frigorifera        kW    2,98  3,97  4,96  7,75  7,75  9,45  9,45  11,94  11,94  12,95  12,95
            Potenza assorbita          kW    0,94  1,29  1,61  2,48  2,64  3,20  3,11  4,14  4,38  4,96  4,91
            Corrente assorbita         A     4,7   6,4   7,9   12,0  4,6   15,0  5,3  20,0   7,3  23,0  8,1

            EER                       W/W    3,17  3,08  3,08  3,12  2,94  2,95  3,04  2,88  2,73  2,61  2,64
            Portata acqua              l/h   504   673   842   1318  1318  1609  1609  2038  2038  2210  2210
            Prevalenza utile           kPa   74,0  74,0  74,0  69,0  69,0  64,0  64,0  52,0  52,0  47,0  47,0
            Prestazioni  in riscaldamento 40 °C / 45 °C (2)
            Potenza termica            kW    4,03  6,04  7,55  10,06  10,06  12,06  12,06  14,05  14,05  15,54  15,54
            Potenza assorbita          kW    1,00  1,58  2,00  2,70  2,70  3,48  3,48  4,18  4,18  4,70  4,70
            Corrente assorbita         A     5,1   7,8   9,7   13,0  4,7   17,0  5,9  20,0   6,9  22,0  7,7
            COP                       W/W    4,03  3,83  3,78  3,72  3,72  3,46  3,46  3,36  3,36  3,31  3,31
            Portata acqua              l/h   710   1062  1326  1762  1762  2110  2110  2456  2456  2714  2714
            Prevalenza utile           kPa   74,0  73,0  71,0  60,0  60,0  50,0  50,0  39,0  39,0  29,0  29,0
            (1)  Dati EN 14511:2022; Acqua scambiatore lato utenza 12 °C / 7 °C; Aria esterna 35 °C
            (2)  Dati EN 14511:2022; Acqua scambiatore lato utenza 40 °C / 45 °C; Aria esterna 7 °C b.s. / 6 °C b.u.
                                            HMI040  HMI060  HMI080  HMI100  HMI100T  HMI120  HMI120T  HMI140  HMI140T  HMI160  HMI160T
            Prestazioni in raffreddamento 23 °C / 18 °C (1)

            Potenza frigorifera        kW    3,77  5,76  6,75  8,75  8,75  10,94  10,94  12,44  12,44  14,45  14,45
            Potenza assorbita          kW    0,82  1,32  1,55  1,96  1,96  2,56  2,56  3,05  3,05  3,82  3,82
            Corrente assorbita         A     4,2   6,6   7,6   9,5   3,6   12,0  4,5  15,0   5,2  18,0  6,4
            EER                       W/W    4,60  4,36  4,36  4,46  4,46  4,27  4,27  4,08  4,08  3,78  3,78
            Portata acqua              l/h   641   982   1152  1495  1495  1873  1873  2132  2132  2478  2478
            Prevalenza utile           kPa   74,0  74,0  73,0  66,0  66,0  57,0  57,0  50,0  50,0  38,0  38,0
            Prestazioni in riscaldamento 30 °C / 35 °C (2)
            Potenza termica            kW    4,03  6,04  7,55  10,06  10,06  12,06  12,06  14,05  14,05  15,54  15,54
            Potenza assorbita          kW    0,79  1,20  1,63  2,17  2,17  2,64  2,64  3,22  3,22  3,60  3,60

            Corrente assorbita         A     4,1   6,0   8,0   11,0  3,9   13,0  4,6  15,0   5,5  17,0  6,1
            COP                       W/W    5,10  5,04  4,63  4,63  4,63  4,57  4,57  4,36  4,36  4,32  4,32
            Portata acqua              l/h   708   1058  1321  1756  1756  2102  2102  2447  2447  2704  2704
            Prevalenza utile           kPa   74,0  73,0  71,0  60,0  60,0  50,0  50,0  39,0  39,0  30,0  30,0
            (1)  Dati EN 14511:2022; Acqua scambiatore lato utenza 23 °C / 18 °C; Aria esterna 35 °C
            (2)  Dati EN 14511:2022; Acqua scambiatore lato utenza 30 °C / 35 °C; Aria esterna 7 °C b.s. / 6 °C b.u.


            HMI-HP_I_UN50_12                           www.aermec.com                                          333
   330   331   332   333   334   335   336   337   338   339   340