Page 498 - AERMEC - CATALOGO PRODOTTI 2023 - DELLAFIORE
P. 498
NRB HE
Taglia 0800 0900 1000 1100 1200 1400 1600 1805 2006 2206 2406 2600 2800 3000 3200 3400 3600
UE 813/2013 prestazioni in condizioni climatiche medie (average) - 55 °C - Pdesignh ≤ 400 kW (1)
Pdesignh kW 204 236 259 290 320 369 318 361 397 440 474 514 544 588 621 666 698
SCOP W/W 3,05 3,08 3,05 3,10 3,03 3,08 3,13 3,05 3,30 3,08 3,15 3,08 3,13 3,03 3,20 3,20 3,13
ηsh % 119,00 120,00 119,00 121,00 118,00 120,00 122,00 119,00 129,00 120,00 123,00 120,00 122,00 118,00 125,00 125,00 122,00
SEER - 12/7 (EN14825: 2018) con ventilatori standard (2)
SEER W/W 4,16 4,15 4,18 4,19 4,16 4,27 4,39 4,36 4,22 - (3) - (3) - (3) - (3) - (3) - (3) - (3) - (3)
Efficienza stagionale % 163,40 163,00 164,10 164,70 163,40 167,90 172,70 171,40 165,80 - (3) - (3) - (3) - (3) - (3) - (3) - (3) - (3)
SEER - 12/7 (EN14825: 2018) con ventilatori inverter (2)
SEER W/W - - - - - - - - - 4,71 4,67 4,74 4,66 4,69 4,62 4,71 4,66
Effi cienza stagionale % - - - - - - - - - 185,4% 183,7% 186,6% 183,4% 184,6% 181,9% 185,4% 183,4%
SEER - 23/18 (EN14825: 2018) con ventilatori standard (4)
SEER W/W - - - - - - - - - 5,17 5,20 5,16 5,01 5,04 4,99 5,03 5,03
Effi cienza stagionale % - - - - - - - - - 203,60 204,90 203,20 197,20 198,60 196,50 198,10 198,10
SEER - 23/18 (EN14825: 2018) con ventilatori inverter
SEER W/W - - - - - - - - - 4,71 4,67 4,74 4,66 4,69 4,62 4,71 4,66
Effi cienza stagionale % - - - - - - - - - - - - - - - - -
SEPR - (EN 14825: 2018) Alta temperatura con ventilatori standard (4)
SEPR W/W - - - - - - - - - 5,52 5,54 5,57 5,52 5,54 5,58 5,56 5,55
SEPR - (EN 14825: 2018) Alta temperatura con ventilatori inverter (4)
SEPR W/W - - - - - - - - - 5,52 5,54 5,57 5,52 5,54 5,58 5,56 5,55
(1) Efficienze in applicazioni per media temperatura (55°C)
(2) Calcolo eseguito con portata d’acqua FISSA e temperatura d’uscita VARIABILE.
(3) Non conformi al regolamento 2016/2281 UE per applicazioni di comfort 12°C / 7°C
(4) Calcolo eseguito con portata d’acqua FISSA.
DATI TECNICI GENERALI
Taglia 0800 0900 1000 1100 1200 1400 1600 1805 2006 2206 2406 2600 2800 3000 3200 3400 3600
Compressore
Tipo °,A,E,L tipo Scroll
Regolazione compressore °,A,E,L Tipo On-Off
Numero °,A,E,L n° 4 4 4 4 4 4 4 5 6 6 6 5 6 6 6 6 6
Circuiti °,A,E,L n° 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
°,A,L tipo R410A
Refrigerante
E tipo
° kg 41,0 42,0 55,0 56,0 56,0 58,0 58,0 84,0 84,0 100,0 100,0 113,0 116,0 138,0 138,0 138,0 143,0
Carica refrigerante (1) A,L kg 43,0 56,0 58,0 58,0 60,0 84,0 87,0 100,0 103,0 116,0 125,0 138,0 138,0 166,0 166,0 183,0 183,0
E kg 56,0 80,0 82,0 82,0 84,0 97,0 113,0 137,0 140,0 153,0 162,0 175,0 175,0 203,0 203,0 220,0 220,0
Scambiatore lato utenza
Tipo °,A,E,L tipo Fascio tubiero
Attacchi idraulici
Attacchi (in/out) °,A,E,L Tipo Giunti scanalati
Attacchi idraulici senza kit idronico
° Ø 5” 5” 5” 5” 5” 5” 5” 6” 6” 6” 6” 6” 6” 6” 6” 6” 6”
Diametro (in/out)
A,E,L Ø 5” 5” 5” 5” 6” 6” 6” 6” 6” 6” 6” 6” 6” 6” 6” 6” 6”
Attacchi idraulici con kit idronico
° Ø - - 3” 3” 3” - - 4” 4” 4” 4” 5” 5” 5” 5” 5” 5”
Diametro (in/out) A,L Ø - 3” - - - 3” 4” 4” 4” 4” 4” 5” 5” 5” 5” 5” 5”
E Ø 3” 3” 3” 3” 3” 3” 4” 4” 4” 4” 4” 5” 5” 5” 5” 5” 5”
(1) La carica riportata in tabella è un valore stimato e preliminare. Il valore finale della carica di refrigerante è riportato nella targhetta tecnica dell’unità. Per maggiori informazioni contattare sede.
Filtro acqua non fornito. Installazione obbligatoria pena decadenza
della garanzia.
496 www.aermec.com NRB-0800-3600-HP-T_I_CE50_08