Page 171 - AERMEC - CATALOGO PRODOTTI 2024 - DELLAFIORE
P. 171
VENTILCONVETTORI VENTILCONVETTORI
DATI PRESTAZIONALI
2 tubi
VDCB100D VDCB200D VDCB300D VDCB500D VDCB700D
1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5
UL L M H HH UL L M H HH UL L M H HH UL L M H HH UL L M H HH
Prestazioni in riscaldamento 45 °C / 35 °C (1)
Potenza termica kW 1,04 1,79 2,58 2,82 4,49 2,18 2,96 3,80 4,08 5,97 2,75 4,14 5,46 5,70 7,06 3,18 5,17 7,02 8,22 11,87 4,37 9,98 12,63 14,64 18,63
Portata acqua utenza l/h 90 155 224 245 390 189 257 329 354 518 238 360 474 495 613 276 449 609 713 1030 379 866 1096 1271 1617
Perdita di carico lato utenza kPa 3 9 17 19 45 15 26 40 46 91 7 16 26 28 41 3 8 14 18 35 3 13 20 26 40
Prestazioni in raffreddamento 5.5 °C / 14.5 °C (2)
Potenza frigorifera kW 0,80 1,37 1,98 2,17 3,45 1,67 2,27 2,92 3,13 4,59 2,11 3,18 4,20 4,38 5,43 2,44 3,97 5,40 6,31 9,12 3,35 7,67 9,71 11,25 14,32
Potenza frigorifera sensibile kW 0,59 1,03 1,51 1,66 2,80 1,19 1,64 2,15 2,33 3,58 1,57 2,43 3,28 3,44 4,40 1,77 2,82 3,77 4,40 6,51 2,93 5,86 7,20 8,20 10,39
Portata acqua utenza l/h 77 131 190 207 330 160 217 279 300 439 202 304 401 419 519 233 380 516 604 872 321 733 928 1075 1369
Perdita di carico lato utenza kPa 3 7 14 17 39 13 22 35 40 79 6 13 22 24 35 3 7 12 16 30 3 11 17 22 34
Prestazioni in raffreddamento 9 °C / 18 °C (3)
Potenza frigorifera kW 0,53 0,90 1,30 1,42 2,27 1,10 1,49 1,92 2,06 3,02 1,39 2,09 2,76 2,88 3,57 1,60 2,61 3,55 4,15 5,99 2,20 5,04 6,38 7,39 9,41
Potenza frigorifera sensibile kW 0,49 0,86 1,27 1,39 2,27 1,00 1,38 1,81 1,96 3,01 1,32 2,04 2,75 2,88 3,57 1,48 2,36 3,17 3,69 5,47 2,20 4,92 6,04 6,89 8,72
Portata acqua utenza l/h 50 86 125 136 217 105 143 183 197 288 133 200 264 275 341 153 249 339 397 573 211 481 610 706 899
Perdita di carico lato utenza kPa 1 3 7 8 18 6 10 16 19 37 3 6 10 11 16 1 3 6 7 14 1 5 8 10 16
Ventilatore
Tipo tipo Centrifugo Centrifugo Centrifugo Centrifugo Centrifugo
Motore ventilatore tipo Inverter Inverter Inverter Inverter Inverter
Numero n° 2 2 3 2 3
Portata aria m³/h 200 287 398 436 800 300 437 585 635 1000 400 606 840 888 1200 600 913 1204 1393 2000 1000 1617 2017 2384 3200
Pressione statica utile Pa 9 26 50 60 43 6 28 50 59 34 3 26 50 56 16 9 29 50 67 19 5 32 50 70 79
Potenza assorbita W 7 15 30 37 80 10 23 45 55 100 14 35 76 93 121 18 50 103 155 249 31 100 166 255 471
Segnale 0-10V % 30 49 69 76 90 30 55 74 81 90 30 61 85 90 90 30 49 66 76 90 30 53 65 75 90
Dati sonori ventilconvettori canalizzati (4)
Livello di potenza sonora (inlet + radiated) dB(A) 35,0 46,0 53,0 54,0 59,0 40,0 50,0 56,0 57,0 62,0 41,0 52,0 58,0 60,0 61,0 44,0 53,0 60,0 63,0 65,0 49,0 62,0 66,0 69,0 73,0
Livello di potenza sonora (outlet) dB(A) 33,0 44,0 50,0 52,0 57,0 37,0 48,0 55,0 56,0 60,0 39,0 50,0 57,0 58,0 60,0 40,0 51,0 57,0 60,0 64,0 43,0 56,0 62,0 66,0 69,0
Alimentazione
Alimentazione 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz
(1) Aria ambiente 20°C b.s.; Acqua (in/out) 45 °C / 35 °C
(2) Aria ambiente 24°C b.s./18 °C b.u.; Acqua (in/out) 5.5 °C / 14.5 °C; EUROVENT
(3) Aria ambiente 26°C b.s./18,6 °C b.u.; Acqua (in/out) 9 °C / 18 °C; EUROVENT
(4) Aermec determina il valore della potenza sonora sulla base di misure effettuate in accordo con la normativa UNI EN 16583:15, nel rispetto della certificazione Eurovent.
Velocità certificate Eurovent: H,M,L
Per le sole unità configurate con la resistenza elettrica (campo 12
del configuratore, opzione H)
VDCB100D VDCB200D VDCB300D VDCB500D VDCB700D
Resistenza elettrica
Numero n° 1 1 1 1 1
Potenza riscaldante kW 1310 1970 2190 2920 4000
VDCBD_I_UN50_00 www.aermec.com 169