MODELLO PUHY-M400YNW-A1(-BS) PUHY-M450YNW-A1(-BS) PUHY-M500YNW-A1(-BS)
HP 16 18 20
Alimentazione Tensione/Freq./Fasi V/Hz/n° 3-phase 4-wire 380-400-415 V 50/60 Hz
Capacità nominale *1 kW 45 50 56
Potenza assorbita kW 14,65 14,70 17,72
Raffreddamento EER* kW 3,07 3,40 3,16
Campo ope- Interna BU °C 15,0~24,0 15,0~24,0 15,0~24,0
rativo
di temperatura Esterna BS °C -5,0~52,0 -5,0~52,0 -5,0~52,0
Capacità nominale *2 kW 50 56 63
Potenza assorbita kW 13,69 16 17.07
Riscaldamento COP* kW 3,65 3,50 3,69
Campo ope- Interna BS °C 15,0~27,0 15,0~27,0 15,0~27,0
rativo
di temperatura Esterna BU °C -20,0~15,5 -20,0~15,5 -20,0~15,5
Livello di pressione 65.0 /67.0 65.5 / 69.5 63.5 / 66.5
(potenza) sonora *3 dB(A) 82.5 / 86.0 83.5 / 88.5 82 / 85.5
Modello/
Unità int. collegabili Quantità W10~125,WL10~50/2~50 W10~125, WL10~50/2~50 W10~125, WL10~50/2~50
Ø est. attacchi refr. mm 12,7/28,58 15,88/28,58 15,88/28,58
Dimensioni esterne ** (AxLxP) mm 1858 x 1240 x 740 1858 x 1240 x 740 1858 x 1750 x 740
Peso netto kg 273 290 329
Carica refr. R32/CO 2 Eq* 4 kg/Tons 9,8/6,62 10,8/7,29 10,8/7,29
*1 Condizioni di raffreddamento nominali: Interno 27°C BS / 19°C BU. Esterno 35°C BS. Lunghezza tubi 7.5 m, differenza livello 0 m.
*2 Condizioni di riscaldamento nominali: Interno 20°C BS. Esterno 7°C BS / 6°C BU. Lunghezza tubi 7.5 m, differenza livello 0 m.
*3 Valori misurati in camera anecoica. Raffreddamento/Riscaldamento
*4 GWP del gas R32 pari a 675 secondo Regolamento 517 / 2014
* I coefficienti prestazionali COP e EER sono prestazioni di sistema e come tali non si riferiscono solo alla unità esterna bensì sono comprensivi sia dei coefficienti di produzione dell’acqua (Unità esterna+Unità Idronica)
che dei coefficienti di distribuzione dell’acqua (Unità Idronica + Unità interne).
** Senza piedi di sostegno rimovibili, A=1798 mm.