Page 504 - AERMEC - CATALOGO PRODOTTI 2024
P. 504
Taglia 0800 0900 1000 1100 1200 1400 1600 1805 2006 2206 2406
SEPR - (EN 14825: 2018) (3)
° W/W 5,39 5,22 5,17 5,03 5,36 5,51 5,52 5,58 5,52 5,51 5,51
A W/W 5,64 5,29 5,58 5,30 5,55 5,52 5,56 5,56 5,57 5,55 5,55
E W/W 5,56 5,22 5,47 5,25 5,52 5,56 5,58 5,54 5,53 5,55 5,55
SEPR
L W/W 5,32 5,05 5,31 5,04 5,18 5,05 5,53 5,53 5,53 5,52 5,54
N W/W 5,69 5,55 5,67 5,60 5,64 5,62 5,66 5,57 5,63 5,60 5,64
U W/W 5,67 5,54 5,66 5,54 5,68 5,59 5,69 5,55 5,55 5,58 5,72
(1) Calcolo eseguito con portata d’acqua FISSA e temperatura d’uscita VARIABILE.
(2) Non conformi al regolamento 2016/2281 UE per applicazioni di comfort 12°C / 7°C
(3) Calcolo eseguito con portata d’acqua FISSA.
DATI ELETTRICI
Taglia 0800 0900 1000 1100 1200 1400 1600 1805 2006 2206 2406
Dati elettrici
° A 164,3 180,7 197,0 226,4 262,1 291,1 320,1 371,3 416,0 445,0 480,4
A,L A 177,1 193,4 222,5 251,8 281,2 310,2 351,9 396,7 454,2 483,2 530,8
Corrente massima (FLA)
E,U A 189,8 206,1 222,5 264,5 293,9 322,9 364,6 428,0 472,8 514,5 543,5
N A 202,5 218,8 235,2 277,3 306,6 335,6 383,2 440,7 485,5 527,2 556,2
° A 352,9 408,1 424,4 477,1 512,8 625,3 654,3 705,5 750,3 779,3 814,6
A,L A 365,6 420,8 449,9 502,5 531,9 644,4 686,1 730,9 788,4 817,4 865,0 ARIA-ACQUA
Corrente di spunto (LRA)
E,U A 378,3 433,5 449,9 515,3 544,6 657,1 698,8 762,2 807,0 848,7 877,7
N A 391,1 446,2 462,6 528,0 557,3 669,8 717,4 774,9 819,7 861,4 890,4
DATI TECNICI GENERALI
Taglia 0800 0900 1000 1100 1200 1400 1600 1805 2006 2206 2406
Compressore
Tipo °,A,E,L,N,U tipo Scroll
Regolazione °,A,E,L,N,U Tipo Asincrono
compressore
Numero °,A,E,L,N,U n° 4 4 4 4 4 4 4 5 6 6 6
Circuiti °,A,E,L,N,U n° 2 2 2 2 2 2 2 2 2 2 2
Refrigerante °,A,E,L,N,U tipo R410A
° kg 14,0 14,5 15,0 16,0 20,5 21,0 21,0 26,0 26,0 26,0 31,0
Carica refrigerante A,L kg 15,0 16,0 20,0 22,0 21,0 22,5 23,5 25,0 30,0 31,0 32,5
circuito 1 (1) E,U kg 20,5 20,0 21,5 26,0 25,0 26,0 30,0 32,0 36,0 44,5 56,0
N kg 25,0 26,5 26,5 29,0 28,0 35,0 42,0 38,0 43,0 62,0 42,0
° kg 14,0 14,5 15,0 16,0 20,5 21,0 21,0 29,0 29,0 29,0 34,0
Carica refrigerante A,L kg 15,0 16,0 20,0 22,0 21,0 22,5 25,5 30,0 34,0 34,0 37,5
circuito 2 (1) E,U kg 20,5 20,0 21,5 27,0 28,0 27,0 32,0 37,0 39,0 45,5 56,0
N kg 25,0 26,5 26,5 30,0 31,0 35,0 42,0 42,0 47,0 62,0 49,0
Potenziale riscalda-
mento globale °,A,E,L,N,U GWP 2088kgCO 2 eq
Scambiatore lato utenza
Tipo °,A,E,L,N,U tipo Piastre
Numero °,A,E,L,N,U n° 1 1 1 1 1 1 1 1 1 1 1
Attacchi idraulici
Attacchi (in/out) °,A,E,L,N,U Tipo Giunti scanalati
Attacchi idraulici senza kit idronico
Diametro (in/out) °,A,E,L,N,U Ø 3” 3” 3” 3” 3” 3” 4” 4” 4” 4” 4”
Attacchi idraulici con kit idronico
Diametro (in/out) °,A,E,L,N,U Ø 3” 3” 3” 3” 3” 3” 4” 4” 4” 4” 4”
(1) La carica riportata in tabella è un valore stimato e preliminare. Il valore finale della carica di refrigerante è riportato nella targhetta tecnica dell’unità. Per maggiori informazioni contattare sede.
Nelle versioni senza kit idronico il filtro acqua viene fornito a corredo con
un tronchetto per il collegamento, viene fornito montato nelle versioni
con il kit idronico.
502 www.aermec.com NRB-0800-3600-CO_I_CE50_13