Page 594 - AERMEC - CATALOGO PRODOTTI 2024
P. 594
TBA - (U)
Taglia 1300 1350 2300 2325 2350 3300 3320 3340 3350 4325
Prestazioni in raffreddamento 12 °C / 7 °C (1)
Potenza frigorifera kW 328,1 443,8 633,5 758,5 876,4 985,0 1088,0 1154,9 1256,9 1342,4
Potenza assorbita kW 92,3 124,4 178,8 213,2 245,5 275,4 306,8 326,3 358,1 386,6
Corrente assorbita totale a freddo A 145,7 200,9 281,4 341,6 401,9 437,1 487,3 522,6 582,6 627,6
EER W/W 3,56 3,57 3,54 3,56 3,57 3,58 3,55 3,54 3,51 3,47
Portata acqua utenza l/h 56452 76308 108940 130424 150669 169356 187070 198556 216075 230760
Perdita di carico lato utenza kPa 51 25 49 50 30 53 56 53 36 38
(1) Dati EN 14511:2022; Acqua scambiatore lato utenza 12 °C / 7 °C; Aria esterna 35 °C
TBA - (N)
Taglia 1300 1350 2300 2325 2350 3300 3320 3340 3350 4325
Prestazioni in raffreddamento 12 °C / 7 °C (1)
Potenza frigorifera kW 328,1 443,8 633,5 758,5 876,4 985,0 1088,0 1154,9 1256,9 1342,4
Potenza assorbita kW 92,3 124,4 178,8 213,2 245,5 275,4 306,8 326,3 358,1 386,6
Corrente assorbita totale a freddo A 145,7 200,9 281,4 341,6 401,9 437,1 487,3 522,6 582,6 627,6
EER W/W 3,56 3,57 3,54 3,56 3,57 3,58 3,55 3,54 3,51 3,47
Portata acqua utenza l/h 56452 76308 108940 130424 150669 169356 187070 198556 216075 230760
Perdita di carico lato utenza kPa 51 25 49 50 30 53 56 53 36 38 ARIA-ACQUA
(1) Dati EN 14511:2022; Acqua scambiatore lato utenza 12 °C / 7 °C; Aria esterna 35 °C
INDICI ENERGETICI (REG. 2016/2281 UE)
Taglia 1300 1350 2300 2325 2350 3300 3320 3340 3350 4325
SEER - 12/7 (EN14825: 2018) con ventilatori inverter (1)
A,E W/W 5,15 5,23 5,48 5,25 5,54 5,54 5,51 5,49 5,57 5,35
SEER
N,U W/W 5,35 5,41 5,60 5,48 5,76 5,80 5,62 5,71 5,73 5,62
A,E % 203,1% 206,0% 216,0% 206,8% 218,4% 218,4% 217,5% 216,5% 219,8% 211,0%
Efficienza stagionale
N,U % 211,0% 213,5% 221,0% 216,1% 227,3% 229,1% 221,9% 225,4% 226,3% 221,6%
SEPR - (EN 14825: 2018) Alta temperatura con ventilatori inverter (2)
A,E W/W 6,31 6,65 6,11 6,32 6,41 6,13 6,26 6,33 6,28 6,12
SEPR
N,U W/W 6,47 6,61 6,52 6,80 6,49 6,62 6,57 6,50 6,47 6,40
(1) Calcolo eseguito con portata d’acqua FISSA e temperatura d’uscita VARIABILE.
(2) Calcolo eseguito con portata d’acqua FISSA.
DATI ELETTRICI
Taglia 1300 1350 2300 2325 2350 3300 3320 3340 3350 4325
Dati elettrici
A,E A 165,0 249,0 319,0 404,0 488,0 483,0 568,0 727,0 727,0 797,0
Corrente massima (FLA)
N,U A 165,0 249,0 329,0 413,0 498,0 493,0 577,0 737,0 737,0 797,0
A,E A 36,0 45,0 200,0 210,0 305,0 374,0 470,0 565,0 565,0 720,0
Corrente di spunto (LRA)
N,U A 36,0 45,0 210,0 305,0 315,0 384,0 479,0 575,0 575,0 720,0
DATI TECNICI GENERALI
Taglia 1300 1350 2300 2325 2350 3300 3320 3340 3350 4325
Compressore
Tipo A,E,N,U tipo Centrifugo
Regolazione compressore A,E,N,U Tipo Inverter
Numero A,E,N,U n° 1 1 2 2 2 3 3 3 3 4
Circuiti A,E,N,U n° 1 1 1 2 1 1 2 1 1 2
Refrigerante A,E,N,U tipo R134a
A,E kg 81,0 166,0 152,0 243,0 285,0 264,0 306,0 317,0 387,0 398,0
Carica refrigerante (1)
N,U kg 81,0 166,0 163,0 254,0 296,0 275,0 317,0 328,0 398,0 398,0
Scambiatore lato utenza
Tipo A,E,N,U tipo Fascio tubiero
Numero A,E,N,U n° 1 1 1 1 1 1 1 1 1 1
Attacchi idraulici
Attacchi (in/out) A,E,N,U Tipo Giunti scanalati
A,E Ø 3” 4” 6” 6” 6” 6” 6” 6” 8” 8”
Diametro (in/out)
N,U Ø 6” 6” 6” 6” 6” 6” 6” 6” 8” 8”
Ventilatore
Tipo A,E,N,U tipo Assiali
Motore ventilatore A,E,N,U tipo Inverter
A,E n° 6 8 10 12 14 16 18 20 20 22
Numero
N,U n° 6 8 12 14 16 18 20 22 22 22
A,E m³/h 112920 150560 188200 225840 263480 301120 338760 376400 376400 414040
Portata aria
N,U m³/h 112920 150560 225840 263480 301120 338760 376400 414040 414040 414040
(1) La carica riportata in tabella è un valore stimato e preliminare. Il valore finale della carica di refrigerante è riportato nella targhetta tecnica dell’unità. Per maggiori informazioni contattare sede.
592 www.aermec.com TBA-CO_I_UN50_06