TBA - (U)
                 Taglia                            1300   1350  2300  2325   2350  3300   3320  3340   3350  4325
                 Prestazioni in raffreddamento 12 °C / 7 °C (1)
                 Potenza frigorifera         kW    328,1  443,8  633,5  758,5  876,4  985,0  1088,0  1154,9  1256,9  1342,4
                 Potenza assorbita           kW    92,3   124,4  178,8  213,2  245,5  275,4  306,8  326,3  358,1  386,6
                 Corrente assorbita totale a freddo  A  145,7  200,9  281,4  341,6  401,9  437,1  487,3  522,6  582,6  627,6
                 EER                         W/W   3,56   3,57  3,54   3,56  3,57   3,58  3,55  3,54   3,51  3,47
                 Portata acqua utenza        l/h   56452  76308  108940  130424  150669  169356  187070  198556  216075  230760
                 Perdita di carico lato utenza  kPa  51   25     49    50     30    53    56     53    36     38
                 (1)  Dati EN 14511:2022; Acqua scambiatore lato utenza 12 °C / 7 °C; Aria esterna 35 °C
                 TBA - (N)
                 Taglia                            1300   1350  2300  2325   2350  3300   3320  3340   3350  4325
                 Prestazioni in raffreddamento 12 °C / 7 °C (1)
                 Potenza frigorifera         kW    328,1  443,8  633,5  758,5  876,4  985,0  1088,0  1154,9  1256,9  1342,4
                 Potenza assorbita           kW    92,3   124,4  178,8  213,2  245,5  275,4  306,8  326,3  358,1  386,6
                 Corrente assorbita totale a freddo  A  145,7  200,9  281,4  341,6  401,9  437,1  487,3  522,6  582,6  627,6
                 EER                         W/W   3,56   3,57  3,54   3,56  3,57   3,58  3,55  3,54   3,51  3,47
                 Portata acqua utenza        l/h   56452  76308  108940  130424  150669  169356  187070  198556  216075  230760
                 Perdita di carico lato utenza  kPa  51   25     49    50     30    53    56     53    36     38             ARIA-ACQUA
                 (1)  Dati EN 14511:2022; Acqua scambiatore lato utenza 12 °C / 7 °C; Aria esterna 35 °C

                 INDICI ENERGETICI (REG. 2016/2281 UE)
                 Taglia                            1300   1350  2300   2325  2350  3300   3320  3340   3350  4325
                 SEER - 12/7 (EN14825: 2018) con ventilatori inverter (1)
                                       A,E   W/W    5,15  5,23   5,48  5,25  5,54   5,54  5,51   5,49  5,57  5,35
                 SEER
                                       N,U   W/W    5,35  5,41   5,60  5,48  5,76   5,80  5,62   5,71  5,73  5,62
                                       A,E    %    203,1%  206,0%  216,0%  206,8%  218,4%  218,4%  217,5%  216,5%  219,8%  211,0%
                 Efficienza stagionale
                                       N,U    %    211,0%  213,5%  221,0%  216,1%  227,3%  229,1%  221,9%  225,4%  226,3%  221,6%
                 SEPR - (EN 14825: 2018) Alta temperatura con ventilatori inverter (2)
                                       A,E   W/W    6,31  6,65   6,11  6,32  6,41   6,13  6,26   6,33  6,28  6,12
                 SEPR
                                       N,U   W/W    6,47  6,61   6,52  6,80  6,49   6,62  6,57   6,50  6,47  6,40
                 (1)  Calcolo eseguito con portata d’acqua FISSA e temperatura d’uscita VARIABILE.
                 (2)  Calcolo eseguito con portata d’acqua FISSA.
                 DATI ELETTRICI
                 Taglia                            1300   1350  2300   2325  2350  3300   3320  3340   3350  4325
                 Dati elettrici
                                       A,E    A    165,0  249,0  319,0  404,0  488,0  483,0  568,0  727,0  727,0  797,0
                 Corrente massima (FLA)
                                       N,U    A    165,0  249,0  329,0  413,0  498,0  493,0  577,0  737,0  737,0  797,0
                                       A,E    A     36,0  45,0  200,0  210,0  305,0  374,0  470,0  565,0  565,0  720,0
                 Corrente di spunto (LRA)
                                       N,U    A     36,0  45,0  210,0  305,0  315,0  384,0  479,0  575,0  575,0  720,0

                 DATI TECNICI GENERALI
                 Taglia                            1300   1350  2300   2325  2350  3300   3320  3340   3350  4325
                 Compressore
                 Tipo                 A,E,N,U  tipo                            Centrifugo
                 Regolazione compressore  A,E,N,U  Tipo                         Inverter
                 Numero               A,E,N,U  n°   1      1     2      2     2     3      3     3      3     4
                 Circuiti             A,E,N,U  n°   1      1     1      2     1     1      2     1      1     2
                 Refrigerante         A,E,N,U  tipo                             R134a
                                       A,E    kg    81,0  166,0  152,0  243,0  285,0  264,0  306,0  317,0  387,0  398,0
                 Carica refrigerante (1)
                                       N,U    kg    81,0  166,0  163,0  254,0  296,0  275,0  317,0  328,0  398,0  398,0
                 Scambiatore lato utenza
                 Tipo                 A,E,N,U  tipo                            Fascio tubiero
                 Numero               A,E,N,U  n°   1      1     1      1     1     1      1     1      1     1
                 Attacchi idraulici
                 Attacchi (in/out)    A,E,N,U  Tipo                           Giunti scanalati
                                       A,E    Ø     3”     4”    6”    6”     6”    6”     6”    6”    8”     8”
                 Diametro (in/out)
                                       N,U    Ø     6”     6”    6”    6”     6”    6”     6”    6”    8”     8”
                 Ventilatore
                 Tipo                 A,E,N,U  tipo                             Assiali
                 Motore ventilatore   A,E,N,U  tipo                             Inverter
                                       A,E    n°    6      8     10    12     14    16     18    20    20     22
                 Numero
                                       N,U    n°    6      8     12    14     16    18     20    22    22     22
                                       A,E   m³/h  112920  150560  188200  225840  263480  301120  338760  376400  376400  414040
                 Portata aria
                                       N,U   m³/h  112920  150560  225840  263480  301120  338760  376400  414040  414040  414040
                 (1)  La carica riportata in tabella è un valore stimato e preliminare. Il valore finale della carica di refrigerante è riportato nella targhetta tecnica dell’unità. Per maggiori informazioni contattare sede.