TBA - (U)
            Taglia                            1300  1350   2300  2325   2350  3300  3320   3340  3350   4325
            Prestazioni in raffreddamento 12 °C / 7 °C (1)

            Potenza frigorifera         kW    328,1  443,8  633,5  758,5  876,4  985,0  1088,0  1154,9  1256,9  1342,4
            Potenza assorbita           kW    92,3  124,4  178,8  213,2  245,5  275,4  306,8  326,3  358,1  386,6
            Corrente assorbita totale a freddo  A  145,7  200,9  281,4  341,6  401,9  437,1  487,3  522,6  582,6  627,6
            EER                        W/W    3,56  3,57   3,54  3,56   3,57  3,58   3,55  3,54  3,51   3,47
            Portata acqua utenza        l/h   56452  76308  108940  130424  150669  169356  187070  198556  216075  230760
            Perdita di carico lato utenza  kPa  51   25    49     50    30     53    56    53     36    38
            (1)  Dati EN 14511:2022; Acqua scambiatore lato utenza 12 °C / 7 °C; Aria esterna 35 °C
               TBA - (N)
            Taglia                            1300  1350   2300  2325   2350  3300  3320   3340  3350   4325
            Prestazioni in raffreddamento 12 °C / 7 °C (1)

            Potenza frigorifera         kW    328,1  443,8  633,5  758,5  876,4  985,0  1088,0  1154,9  1256,9  1342,4
            Potenza assorbita           kW    92,3  124,4  178,8  213,2  245,5  275,4  306,8  326,3  358,1  386,6
            Corrente assorbita totale a freddo  A  145,7  200,9  281,4  341,6  401,9  437,1  487,3  522,6  582,6  627,6
            EER                        W/W    3,56  3,57   3,54  3,56   3,57  3,58   3,55  3,54  3,51   3,47
            Portata acqua utenza        l/h   56452  76308  108940  130424  150669  169356  187070  198556  216075  230760
            Perdita di carico lato utenza  kPa  51   25    49     50    30     53    56    53     36    38
            (1)  Dati EN 14511:2022; Acqua scambiatore lato utenza 12 °C / 7 °C; Aria esterna 35 °C

              INDICI ENERGETICI (REG. 2016/2281 UE)
            Taglia                            1300   1350  2300  2325   2350  3300  3320   3340  3350   4325
            SEER - 12/7 (EN14825: 2018) con ventilatori inverter (1)
                                  A,E   W/W   5,15   5,23  5,48   5,25  5,54  5,54   5,51  5,49   5,57  5,35
            SEER
                                  N,U   W/W   5,35   5,41  5,60   5,48  5,76  5,80   5,62  5,71   5,73  5,62
                                  A,E   %     203,1%  206,0%  216,0%  206,8%  218,4%  218,4%  217,5%  216,5%  219,8%  211,0%
            Effi  cienza stagionale
                                  N,U   %     211,0%  213,5%  221,0%  216,1%  227,3%  229,1%  221,9%  225,4%  226,3%  221,6%
            SEPR - (EN 14825: 2018) Alta temperatura con ventilatori inverter (2)
                                  A,E   W/W   6,31   6,65  6,11   6,32  6,41  6,13   6,26  6,33   6,28  6,12
            SEPR
                                  N,U   W/W   6,47   6,61  6,52   6,80  6,49  6,62   6,57  6,50   6,47  6,40
            (1)  Calcolo eseguito con portata d’acqua FISSA e temperatura d’uscita VARIABILE.
            (2)  Calcolo eseguito con portata d’acqua FISSA.
              DATI ELETTRICI
            Taglia                            1300   1350  2300  2325   2350  3300  3320   3340  3350   4325
            Dati elettrici
                                  A,E    A    165,0  249,0  319,0  404,0  488,0  483,0  568,0  727,0  727,0  797,0
            Corrente massima (FLA)
                                  N,U    A    165,0  249,0  329,0  413,0  498,0  493,0  577,0  737,0  737,0  797,0
                                  A,E    A    36,0   45,0  200,0  210,0  305,0  374,0  470,0  565,0  565,0  720,0
            Corrente di spunto (LRA)
                                  N,U    A    36,0   45,0  210,0  305,0  315,0  384,0  479,0  575,0  575,0  720,0

              DATI TECNICI GENERALI
            Taglia                            1300   1350  2300  2325   2350  3300  3320   3340  3350   4325
            Compressore
            Tipo                 A,E,N,U  tipo                            Centrifugo
            Regolazione compressore  A,E,N,U  Tipo                        Inverter
            Numero               A,E,N,U  n°   1     1      2     2      2     3     3      3     3      4
            Circuiti             A,E,N,U  n°   1     1      1     2      1     1     2      1     1      2
            Refrigerante         A,E,N,U  tipo                             R134a
                                  A,E   kg    81,0  166,0  152,0  243,0  285,0  264,0  306,0  317,0  387,0  398,0
            Carica refrigerante (1)
                                  N,U   kg    81,0  166,0  163,0  254,0  296,0  275,0  317,0  328,0  398,0  398,0
            Scambiatore lato utenza
            Tipo                 A,E,N,U  tipo                           Fascio tubiero
            Numero               A,E,N,U  n°   1     1      1     1      1     1     1      1     1      1
            Attacchi idraulici
            Attacchi (in/out)    A,E,N,U  Tipo                           Giunti scanalati
                                  A,E    Ø     3”    4”     6”    6”    6”     6”    6”     6”    8”    8”
            Diametro (in/out)
                                  N,U    Ø     6”    6”     6”    6”    6”     6”    6”     6”    8”    8”
            Ventilatore
            Tipo                 A,E,N,U  tipo                             Assiali
            Motore ventilatore   A,E,N,U  tipo                            Inverter
                                  A,E   n°     6     8      10    12    14     16    18     20    20    22
            Numero
                                  N,U   n°     6     8      12    14    16     18    20     22    22    22
                                  A,E   m³/h  112920  150560  188200  225840  263480  301120  338760  376400  376400  414040
            Portata aria
                                  N,U   m³/h  112920  150560  225840  263480  301120  338760  376400  414040  414040  414040