Page 578 - AERMEC - CATALOGO PRODOTTI 2024
P. 578
DATI ELETTRICI
Taglia 1251 1401 1402 1601 1602 1801 1802 2002 2202
Dati elettrici
Corrente massima (FLA) A,E A 209,0 242,0 276,0 258,0 276,0 316,0 325,0 352,0 370,0
Corrente di spunto (LRA) A,E A 327,0 387,0 251,0 431,0 251,0 472,0 305,0 313,0 350,0
Taglia 2352 2502 2652 2802 3002 3202 3402 3602
Dati elettrici
Corrente massima (FLA) A,E A 390,0 410,0 443,0 476,0 500,0 516,0 574,0 631,0
Corrente di spunto (LRA) A,E A 365,0 436,0 461,0 521,0 534,0 578,0 612,0 653,0
DATI TECNICI GENERALI
Taglia 1251 1401 1402 1601 1602 1801 1802 2002 2202 2352 2502 2652 2802 3002 3202 3402 3602
Compressore
Tipo A,E tipo Vite
Regolazione compressore A,E Tipo On/Off
Numero A,E n° 1 1 2 1 2 1 2 2 2 2 2 2 2 2 2 2 2
Circuiti A,E n° 1 1 2 1 2 1 2 2 2 2 2 2 2 2 2 2 2
Parzializzazione dell’unità con A % 40-100 40-100 20-100 40-100 20-100 40-100 20-100 20-100 20-100 20-100 20-100 20-100 20-100 20-100 20-100 20-100 20-100
valvola termostatica elettronica E % - - - - - - - - - - - - - - - - -
Refrigerante A,E tipo R134a ARIA-ACQUA
A kg 90,0 92,0 43,0 100,0 57,0 138,0 57,0 55,0 80,0 80,0 85,0 - 97,0 92,0 - 110,0 138,0
Carica refrigerante circuito 1 (1)
E kg 90,0 92,0 43,0 118,0 57,0 138,0 57,0 55,0 80,0 80,0 85,0 - 97,0 92,0 118,0 110,0 138,0
A kg - - 45,0 - 57,0 - 57,0 75,0 102,0 85,0 85,0 - 97,0 100,0 - 145,0 138,0
Carica refrigerante circuito 2 (1)
E kg - - 45,0 - 57,0 - 57,0 75,0 102,0 85,0 85,0 - 97,0 118,0 118,0 145,0 138,0
Carica olio totale A,E kg 22,0 19,0 30,0 19,0 30,0 35,0 30,0 30,0 30,0 37,0 44,0 41,0 38,0 38,0 38,0 54,0 70,0
Scambiatore lato utenza
Tipo A,E tipo Fascio tubiero
Numero A,E n° 1 1 2 1 2 1 2 2 1 1 1 1 1 2 2 2 2
A l/h 22593 24226 22164 26631 27146 31442 31442 33074 35651 39087 42953 45101 47077 50856 53262 58072 62883
Portata minima acqua
E l/h 21563 22937 20875 25171 25944 29552 30067 31528 33933 37455 41922 43554 44499 48107 50341 54722 59103
A l/h 75310 80752 73878 88770 90487 104805 104805 110245 118837 130290 143177 150335 156922 169520 177538 193573 209610
Portata massima acqua
E l/h 71875 76457 69583 83902 86478 98505 100223 105092 113108 124850 139740 145180 148330 160357 167802 182407 197010
Contenuto acqua A,E l 96,0 101,2 96,0 98,1 101,2 132,9 132,9 132,9 159,8 159,8 149,9 220,7 220,7 199,3 196,2 231,0 265,8
Attacchi idraulici lato utenza
Attacchi (in/out) A,E Tipo Giunti scanalati
Diametro (in/out) A,E Ø 6”
Dati sonori calcolati in funzionamento a freddo (2)
A dB(A) 93,5 93,5 94,0 94,5 95,0 96,0 96,0 96,5 96,5 96,5 97,0 97,0 97,0 97,0 97,5 98,3 99,0
Livello di potenza sonora
E dB(A) 88,5 88,5 89,0 89,5 90,0 91,0 91,0 91,5 91,5 91,5 92,0 92,0 92,0 92,0 92,5 93,3 94,0
A dB(A) 61,3 61,3 61,8 62,3 62,8 63,6 63,6 64,0 64,0 64,0 64,5 64,5 64,5 64,4 64,9 65,6 66,2
Livello di pressione sonora (10 m)
E dB(A) 56,3 56,3 56,8 57,3 57,8 58,6 58,6 59,0 59,0 59,0 59,5 59,5 59,5 57,4 59,9 60,6 61,2
A dB(A) 73,8 73,8 74,3 74,8 75,3 75,8 75,8 75,9 75,9 75,9 76,4 76,4 76,4 75,8 76,3 76,8 77,2
Livello di pressione sonora (1 m)
E dB(A) 68,8 68,8 69,3 69,8 70,3 70,8 70,8 70,9 70,9 70,9 71,4 71,4 71,4 70,8 71,3 71,8 72,2
(1) La carica riportata in tabella è un valore stimato e preliminare. Il valore finale della carica di refrigerante è riportato nella targhetta tecnica dell’unità. Per maggiori informazioni contattare sede.
(2) Potenza sonora: calcolata sulla base di misure effettuate in accordo con la normativa UNI EN ISO 9614-2, nel rispetto di quanto richiesto dalla certificazione Eurovent.; Pressione sonora misurata in campo libero, a 10 m di distanza dalla
superficie esterna dell’unità (in accordo con la UNI EN ISO 3744).
576 www.aermec.com NSH-1251-3602-HP_I_UN50_06