MVA220DV MVA280DV MVA360DV MVA450DV MVA560DV MVA630DV MVA710DV
Prestazioni in raffrescamento nominali
Potenza frigorifera (1) kW 2,20 2,80 3,60 4,50 5,60 6,30 7,10
Prestazioni in riscaldamento nominali
Potenza termica (2) kW 2,50 3,20 4,00 5,00 6,30 7,10 8,00
Dati elettrici
Potenza nominale assorbita (3) W 35 35 43 45 80 80 90
Ventilatore
Tipo tipo Centrifugo inverter Centrifugo inverter Centrifugo inverter Centrifugo inverter Centrifugo inverter Centrifugo inverter Centrifugo inverter
Portata d’aria
Minima m³/h 250 250 350 400 600 600 700
Media m³/h 350 350 450 500 750 750 900
Massima m³/h 450 450 550 650 900 900 1100
Pressione statica utile
Nominale Pa 10 10 10 15 15 15 15
Minima Pa 0 0 0 0 0 0 0
Massima Pa 40 40 40 60 60 60 60
Potenza sonora (4)
Minima dB(A) 35,0 35,0 38,0 38,0 40,0 40,0 43,0
Media dB(A) 38,0 38,0 41,0 41,0 43,0 43,0 45,0
Massima dB(A) 40,0 40,0 43,0 43,0 45,0 45,0 47,0
Pressione sonora (5)
Minima dB(A) 25,0 25,0 28,0 28,0 30,0 30,0 33,0
Media dB(A) 28,0 28,0 31,0 31,0 33,0 33,0 35,0
Massima dB(A) 30,0 30,0 33,0 33,0 35,0 35,0 37,0
Tubazioni frigorifere
Diametro attacchi frigoriferi liquido mm (inch) 6,35 (1/4”) 6,35 (1/4”) 6,35 (1/4”) 6,35 (1/4”) 9,52 (3/8”) 9,52 (3/8”) 9,52 (3/8”)
Diametro attacchi frigoriferi gas mm (inch) 9,52 (3/8”) 9,52 (3/8”) 12,7 (1/2”) 12,7 (1/2”) 15,9 (5/8”) 15,9 (5/8”) 15,9 (5/8”)
Alimentazione
Alimentazione unità interna 220-240V ~ 50Hz 220-240V ~ 50Hz 220-240V ~ 50Hz 220-240V ~ 50Hz 220-240V ~ 50Hz 220-240V ~ 50Hz 220-240V ~ 50Hz
Unità interna
Diametro scarico condensa mm 25,0 25,0 25,0 25,0 25,0 25,0 25,0
(1) Raffrescamento (EN 14511 e EN 14825) temperatura aria ambiente 27 °C b.s. / 19 °C b.u.; temperatura aria esterna 35 °C; velocità turbo; lunghezza linee frigorifere 5 m.
(2) Riscaldamento (EN 14511 e EN 14825) temperatura aria ambiente 20 °C b.s.; temperatura aria esterna 7 °C b.s. / 6 °C b.u.; velocità turbo; lunghezza linee frigorifere 5 m.
(3) La potenza nominale assorbita (corrente nominale assorbita), è la massima potenza elettrica assorbita (corrente massima assorbita) dal sistema, in accordo con la normativa EN 60335-1 e EN 60335-2-40.
(4) Potenza sonora calcolata in campo libero in accordo con UNI EN ISO 3744.
(5) Pressione sonora misurata in camera anecoica a 1,5 m di distanza frontale.
MVA_CS
MVA151CS MVA181CS MVA221CS MVA281CS MVA361CS MVA451CS MVA501CS MVA561CS
Prestazioni in raffrescamento nominali
Potenza frigorifera (1) kW 1,50 1,80 2,20 2,80 3,60 4,50 5,00 5,60
Prestazioni in riscaldamento nominali
Potenza termica (2) kW 1,80 2,20 2,50 3,20 4,00 5,00 5,60 6,30
Dati elettrici
Potenza nominale assorbita (3) W 30 30 30 30 30 45 45 45
Ventilatore
Tipo tipo Centrifugo inverter Centrifugo inverter Centrifugo inverter Centrifugo inverter Centrifugo inverter Centrifugo inverter Centrifugo inverter Centrifugo inverter
Portata d’aria
Minima m³/h 370 370 370 420 480 560 560 560
Media m³/h 420 420 460 480 550 650 650 650
Massima m³/h 460 460 500 570 620 730 730 730
Potenza sonora (4)
Minima dB(A) 39,0 39,0 39,0 42,0 45,0 53,0 43,0 53,0
Media dB(A) 44,0 44,0 45,0 47,0 49,0 55,0 55,0 55,0
Massima dB(A) 47,0 47,0 50,0 50,0 52,0 57,0 57,0 57,0
Pressione sonora (5)
Minima dB(A) 25,0 25,0 25,0 28,0 31,0 39,0 39,0 39,0
Media dB(A) 30,0 30,0 31,0 33,0 35,0 41,0 41,0 41,0
Massima dB(A) 33,0 33,0 36,0 36,0 38,0 43,0 43,0 43,0
Tubazioni frigorifere
Diametro attacchi frigoriferi liquido mm (inch) 6,35 (1/4”) 6,35 (1/4”) 6,35 (1/4”) 6,35 (1/4”) 6,35 (1/4”) 6,35 (1/4”) 6,35 (1/4”) 9,52 (3/8”)
Diametro attacchi frigoriferi gas mm (inch) 9,52 (3/8”) 9,52 (3/8”) 9,52 (3/8”) 9,52 (3/8”) 12,7 (1/2”) 12,7 (1/2”) 12,7 (1/2”) 15,9 (5/8”)
Alimentazione
Alimentazione unità interna 220-240V ~ 50Hz 220-240V ~ 50Hz 220-240V ~ 50Hz 220-240V ~ 50Hz 220-240V ~ 50Hz 220-240V ~ 50Hz 220-240V ~ 50Hz 220-240V ~ 50Hz
SISTEMI VRF Unità interna mm 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 SISTEMI VRF
Diametro scarico condensa
(1) Raffrescamento (EN 14511 e EN 14825) temperatura aria ambiente 27 °C b.s. / 19 °C b.u.; temperatura aria esterna 35 °C; velocità turbo; lunghezza linee frigorifere 5 m.
(2) Riscaldamento (EN 14511 e EN 14825) temperatura aria ambiente 20 °C b.s.; temperatura aria esterna 7 °C b.s. / 6 °C b.u.; velocità turbo; lunghezza linee frigorifere 5 m.
(3) La potenza nominale assorbita (corrente nominale assorbita), è la massima potenza elettrica assorbita (corrente massima assorbita) dal sistema, in accordo con la normativa EN 60335-1 e EN 60335-2-40.
(4) Potenza sonora calcolata in campo libero in accordo con UNI EN ISO 3744.
(5) Pressione sonora misurata in camera anecoica a 1,5 m di distanza frontale.
MVBM_I_UN50_03 www.aermec.com 935