DATI PRESTAZIONALI
                 NSMI - A/E
                 Taglia                       1251  1601  1801  2352  2652  2802  3202  3402  3802  4102  4402  4802  5202  5702  6102
                 Prestazioni in raffreddamento 12 °C / 7 °C (1)
                 Potenza frigorifera      kW  285,6  382,0  464,0  519,1  605,4  659,4  725,2  802,4  842,6  948,0  1008,8  1110,4  1204,3  1253,0  1342,6
                 Potenza assorbita        kW   91,3  120,2  149,5  167,1  194,3  212,3  232,7  257,5  269,9  304,8  324,7  356,2  397,4  415,9  454,6
                 Corrente assorbita totale a freddo  A  155,0  200,0  245,0  293,0  337,0  360,0  393,0  431,0  443,0  517,0  547,0  619,0  665,0  728,0  761,0
                 EER                      W/W  3,13  3,18  3,10  3,11  3,12  3,11  3,12  3,12  3,12  3,11  3,11  3,12  3,03  3,01  2,95
                 Portata acqua utenza      l/h  49130  65700  79773  89247  104092 113376 124682 137945 144852 162983 173442 190903 207040 215409 230815
                 Perdita di carico lato utenza  kPa  45  15  21  18  25  28  33  27  30  39  45  38   44  49   55
                 (1)  Dati EN 14511:2022; Acqua scambiatore lato utenza 12 °C / 7 °C; Aria esterna 35 °C

                 INDICI ENERGETICI (REG. 2016/2281 UE)
                 Taglia                         1251  1601  1801  2352  2652  2802  3202  3402  3802  4102  4402  4802  5202  5702  6102
                 SEER - 12/7 (EN14825: 2018) con ventilatori standard (1)
                 SEER                  A,E  W/W  4,75  4,82  4,78  4,90  4,92  4,90  4,91  4,93  4,93  4,90  4,88  4,90  4,85  4,70  4,69
                 Efficienza stagionale  A,E  %  186,8% 189,7% 188,0% 193,1% 193,9% 193,0% 193,3% 194,2% 194,3% 192,8% 192,2% 192,9% 191,0% 185,1% 184,7%
                 SEER - 12/7 (EN14825: 2018) con ventilatori inverter (1)
                 SEER                  A,E  W/W  4,95  5,04  5,00  5,01  5,03  5,01  5,02  5,04  5,04  5,00  4,99  5,00  4,96  4,81  4,80
                 Efficienza stagionale  A,E  %  194,9% 198,4% 196,8% 197,3% 198,1% 197,2% 197,6% 198,5% 198,5% 197,1% 196,4% 197,1% 195,3% 189,2% 188,8%    ARIA-ACQUA
                 SEPR - (EN 14825: 2018) Alta temperatura con ventilatori standard (2)
                 SEPR                  A,E  W/W  5,70  5,62  5,59  6,56  6,43  6,42  6,77  6,94  7,21  6,96  7,47  6,88  7,21  6,69  7,01
                 SEPR - (EN 14825: 2018) Alta temperatura con ventilatori inverter (2)
                 SEPR                  A,E  W/W  5,70  5,62  5,59  6,56  6,43  6,42  6,77  6,94  7,21  6,96  7,47  6,88  7,21  6,69  7,01
                 (1)  Calcolo eseguito con portata d’acqua FISSA e temperatura d’uscita VARIABILE.
                 (2)  Calcolo eseguito con portata d’acqua FISSA.

                 DATI ELETTRICI
                 Taglia                     1251  1601  1801  2352  2652  2802  3202  3402  3802  4102  4402  4802  5202  5702  6102
                 Dati elettrici
                 Corrente massima (FLA)  A,E  A  251,3  291,3  377,7  442,0  473,0  519,4  519,4  567,4  653,8  708,1  753,5  874,8  917,2  1002,2  1036,2
                 Corrente di spunto (LRA)  A,E  A  51,3  51,3  57,7  571,7  605,0  651,4  651,4  775,4  861,8  989,1  1059,4  1180,2  1335,2  1420,2  1532,2

                 DATI TECNICI GENERALI
                 Taglia                         1251  1601  1801  2352  2652  2802  3202  3402  3802  4102  4402  4802  5202  5702  6102
                 Compressore
                 Tipo                  A,E  tipo                                Vite
                 Regolazione compressore  A,E  Tipo  I  I  I  1+I  1+I  1+I  1+I  1+I  1+I  1+I  1+I  1+I  1+I  1+I  1+I
                 Numero                A,E   n°  1    1   1    2   2   2    2   2    2   2   2    2   2    2   2
                 Circuiti              A,E   n°  1    1   1    2   2   2    2   2    2   2   2    2   2    2   2
                 Refrigerante          A,E  tipo                               R134a
                 Carica refrigerante (1)  A,E  kg  28,0  28,0  30,0  81,0  92,0  110,0  114,0  107,0  131,0  146,0  163,0  183,0  183,0  195,0  195,0
                 Scambiatore lato utenza
                 Tipo                  A,E  tipo                              Fascio tubiero
                 Numero                A,E   n°  1    1   1    1   1   1    1   1    1   1   1    1   1    1   1
                 Attacchi idraulici
                 Attacchi (in/out)     A,E  Tipo                             Giunti scanalati
                 Diametro (in/out)     A,E   Ø   5”   6”  6”  6”   6”  6”   6”  8”  8”   8”  8”  10”  10”  10”  10”
                 (1)  La carica riportata in tabella è un valore stimato e preliminare. Il valore finale della carica di refrigerante è riportato nella targhetta tecnica dell’unità. Per maggiori informazioni contattare sede.
                 Ventilatori
                 Taglia                         1251  1601  1801  2352  2652  2802  3202  3402  3802  4102  4402  4802  5202  5702  6102
                 Ventilatori: °
                 Ventilatore
                 Tipo                  A,E  tipo                               Assiale
                 Motore ventilatore    A,E  tipo                           Asincrono con taglio di fase
                 Numero                A,E   n°  8    8   10  10   12  14   14  14  16   18  20   22  22  22   22
                 Portata aria          A,E  m³/h  128000 128000 160000 160000 192000 224000 224000 224000 256000 288000 320000 396000 396000 396000 396000
                 Dati sonori
                 Taglia                         1251  1601  1801  2352  2652  2802  3202  3402  3802  4102  4402  4802  5202  5702  6102
                 Dati sonori calcolati in funzionamento a freddo (1)
                                       A    dB(A)  97,2  98,6  98,6  98,6  98,8  99,9  99,9  100,3  100,3  100,4  101,0  102,9  103,2  102,9  103,2
                 Livello di potenza sonora
                                       E    dB(A)  92,9  95,8  95,9  94,7  95,1  96,1  96,1  97,3  97,4  97,7  98,0  99,9  99,9  99,9  99,9
                                       A    dB(A)  64,8  66,2  66,1  66,1  66,2  67,1  67,1  67,5  67,5  67,4  67,9  69,7  69,9  69,7  69,9
                 Livello di pressione sonora (10 m)
                                       E    dB(A)  60,6  63,4  63,4  62,1  62,5  63,3  63,3  64,6  64,5  64,7  64,8  66,7  66,7  66,7  66,7
                 (1)  Potenza sonora: calcolata sulla base di misure effettuate in accordo con la normativa UNI EN ISO 9614-2, nel rispetto di quanto richiesto dalla certificazione Eurovent.; Pressione sonora misurata in campo libero, a 10 m di distanza dalla
                   superficie esterna dell’unità (in accordo con la UNI EN ISO 3744).