Unità interna                        LCG1000D        LCG1200D        LCG1400D        LCG1600D
             Unità esterna                        LCG1000T        LCG1200T        LCG1400T        LCG1600T
             Prestazioni in raffrescamento nominali
             Potenza frigorifera (1)    kW         10,00           12,10           13,40           16,00
             Potenza assorbita a freddo (1)  kW     3,15            3,80            4,70            5,45
             EER (2)                   W/W          3,17            3,18            2,85            2,94
             Umidità asportata          l/h         2,8             2,0             3,6             4,3
             Prestazioni in raffrescamento minime e massime
             Potenza frigorifera  min / max  kW   3,20/11,00      3,60/12,80      6,00/14,20      6,80/16,80
             Potenza assorbita a freddo  min / max  kW  0,60/4,05  0,60/5,30      0,80/5,95       0,85/5,95
             Corrente assorbita a freddo  max  A    4,8             5,3             7,2             7,7
             Efficienza stagionale
             SEER                      W/W          6,10            5,80            5,60            6,10
             Classe efficienza energetica (3)      A++              -               -                -
             Pdesignc                   kW          10,0            -               -                -
             Consumo elettrico annuo  kWh/annum     577             -               -                -
             Prestazioni in riscaldamento nominali
             Potenza termica (4)        kW         12,00           13,50           15,50           17,00
             Potenza assorbita a caldo (4)  kW      3,50            3,90            4,45            5,00
             COP (2)                   W/W          3,43            3,46            3,48            3,40
             Prestazioni in riscaldamento minime e massime
             Potenza termica  min / max  kW       3,00/13,50      3,60/14,50      3,90/16,00      4,50/17,50
             Potenza assorbita a caldo  min / max  kW  0,60/4,05  0,60/5,30       0,80/5,95       0,85/5,95
             Efficienza stagionale (clima temperato)
             SCOP                                   4,00            -               -                -
             Classe efficienza energetica (3)       A+              -               -                -
             Pdesignh                   kW          9,0             -               -                -
             Consumo elettrico annuo  kWh/annum    3218             -               -                -

             Dati elettrici
             Potenza nominale assorbita (5)  kW     4,7             5,3             6,0             6,0
             Corrente nominale assorbita (5)  A     7,0             8,0             9,0             9,0
             Ventilatore
             Tipo di ventilatore        Tipo                            Centrifugo inverter
             Portata d’aria                           turbo/max/med/min  m /h  1800/1520/1380/1270  2000/1730/1570/1400  2200/2000/1730/1490  2400/1960/1670/1380
                                        3
             Pressione statica utile             nominale/min/max  Pa  37/0/150  50/0/150  50/0/150  50/0/200
             Pressione sonora (6)              turbo/max/med/min  dB(A)  46,0/44,0/42,0/40,0  42,0/40,0/39,0/37,0  43,0/41,0/40,0/38,0  44,0/41,0/39,0/38,0
             Tubazioni frigorifere
             Diametro attacchi frigoriferi   mm (inch)  9,52 (3/8”)  9,52 (3/8”)  9,52 (3/8”)     9,52 (3/8”)
             liquido
             Diametro attacchi frigoriferi gas  mm (inch)  15,9 (5/8")  15,9 (5/8")  15,9 (5/8")  15,9 (5/8")
             Diametro scarico condensa  mm          26,0            26,0            26,0            26,0
             Alimentazione                      380-415V 3N ~ 50Hz  380-415V 3N ~ 50Hz  380-415V 3N ~ 50Hz  380-415V 3N ~ 50Hz
             Dimensioni                 mm       1000X700X300    1400X700X300    1400X700X300    1400X700X300
            (1)  Raffrescamento (EN 14511 e EN 14825) temperatura aria ambiente 27 °C b.s. / 19 °C b.u.; temperatura aria esterna 35 °C; velocità turbo; lunghezza linee frigorifere 5 m.
            (2)  EER/COP in accordo alla Normativa (EN 14511), dichiarati solo al fine delle detrazioni fiscali in vigore all’atto della realizzazione di questa pubblicazione.
            (3)  Dati in accordo con il regolamento delegato (UE) N.626/2011.
            (4)  Riscaldamento (EN 14511 e EN 14825) temperatura aria ambiente 20 °C b.s.; temperatura aria esterna 7 °C b.s. / 6 °C b.u.; velocità turbo; lunghezza linee frigorifere 5 m.
            (5)  La potenza nominale assorbita (corrente nominale assorbita), è la massima potenza elettrica assorbita (corrente massima assorbita) dal sistema, in accordo con la normativa EN 60335-1 e EN 60335-2-40.
            (6)  Pressione sonora misurata in camera anecoica a 1,5 m di distanza frontale.



















                                                            37