Page 42 - AERMEC - SPLIT SYSTEM-SISTEMI VRF - DELLAFIORE
P. 42
LCG_F
Unità interna LCG350F LCG500F LCG700F LCG850F LCG1000F LCG1200F LCG1400F
Unità esterna LCG350 LCG500 LCG700 LCG850 LCG1000 LCG1200 LCG1400
Prestazioni in raffrescamento nominali
Potenza frigorifera (1) kW 3,50 5,00 7,00 8,50 10,00 12,10 13,40
Potenza assorbita a freddo (1) kW 0,95 1,55 1,90 2,80 3,30 3,90 4,40
EER (2) W/W 3,89 3,23 3,68 3,04 3,03 3,10 3,05
Umidità asportata l/h 0,5 1,6 1,4 2,6 3,1 3,3 3,3
Prestazioni in raffrescamento minime e massime
Potenza frigorifera min / max kW 0,90/4,00 1,60/5,50 2,40/8,00 2,40/9,00 3,20/11,00 3,60/12,80 6,00/14,20
Potenza assorbita a freddo min / max kW 0,20/1,35 0,30/1,75 0,40/3,50 0,50/3,95 0,60/4,05 0,70/4,85 0,80/5,50
Corrente assorbita a freddo max A 4,0 6,5 8,6 12,7 14,5 15,7 19,5
Efficienza stagionale
SEER W/W 6,7 6,1 6,8 6,1 6,1 6,1 6,3
Classe efficienza energetica (3) A++ A++ A++ A++ A++ - -
Pdesignc kW 3,5 5,0 7,0 8,5 10,0 - -
kWh/
Consumo elettrico annuo 177 284 359 477 573 - -
annum
Prestazioni in riscaldamento nominali
Potenza termica (4) kW 4,00 5,50 8,00 8,80 12,00 13,50 15,50
Potenza assorbita a caldo (4) kW 1,05 1,60 2,45 2,65 3,60 3,95 4,35
COP (2) W/W 4,21 3,44 3,27 3,32 3,33 3,42 3,56
Prestazioni in riscaldamento minime e massime
Potenza termica min / max kW 0,90/4,50 1,50/6,00 2,20/9,00 2,40/9,50 3,00/13,50 3,60/14,50 3,90/16,00
Potenza assorbita a caldo min / max kW 0,20/1,35 0,30/1,75 0,45/3,50 0,50/3,95 0,60/4,05 0,70/4,85 0,80/5,50
Efficienza stagionale (clima temperato)
SCOP 4,0 4,0 3,9 4,0 4,0 3,8 3,7
Classe efficienza energetica (3) A+ A+ A A+ A+ - -
Pdesignh kW 3,1 4,0 6,4 7,2 9,0 - -
kWh/
Consumo elettrico annuo 1040 1394 2295 2577 3149 - -
annum
Dati elettrici
Potenza nominale assorbita (5) kW 1,4 1,8 3,5 4,0 4,1 4,9 5,5
Corrente nominale assorbita (5) A 6,0 8,0 16,0 18,0 18,5 22,0 25,0
Ventilatore
Tipo di ventilatore Tipo Centrifugo inverter
Portata d’aria turbo/max/med/min m /h 650/610/530/460 850/800/700/600 1300/1220/1090/940 1500/1380/1200/1020 1600/1500/1350/1260 1800/1700/1540/1400 2100/2000/1800/1480
3
Pressione sonora (6) turbo/max/med/min dB(A) 39,0/36,0/32,0/28,0 44,0/42,0/39,0/36,0 45,0/44,0/41,0/38,0 49,0/47,0/43,0/39,0 49,0/47,0/45,0/43,0 49,0/47,0/44,0/42,0 52,0/50,0/48,0/44,0
Tubazioni frigorifere
mm
Diametro attacchi frigoriferi liquido 6,35 (1/4”) 6,35 (1/4") 9,52 (3/8") 9,52 (3/8") 9,52 (3/8") 9,52 (3/8") 9,52 (3/8")
(inch)
mm
Diametro attacchi frigoriferi gas 9,52 (3/8”) 12,7 (1/2") 15,9 (5/8") 15,9 (5/8") 15,9 (5/8") 15,9 (5/8") 15,9 (5/8")
(inch)
Diametro scarico condensa mm 17,0 17,0 17,0 17,0 17,0 17,0 17,0
Alimentazione 220-240V ~ 50Hz
Dimensioni mm 870X235X665 870X235X665 1200X235X665 1200X235X665 1200X235X665 1570X235X665 1570X235X665
(1) Raffrescamento (EN 14511 e EN 14825) temperatura aria ambiente 27 °C b.s. / 19 °C b.u.; temperatura aria esterna 35 °C; velocità turbo; lunghezza linee frigorifere 5 m.
(2) EER/COP in accordo alla Normativa (EN 14511), dichiarati solo al fine delle detrazioni fiscali in vigore all’atto della realizzazione di questa pubblicazione.
(3) Dati in accordo con il regolamento delegato (UE) N.626/2011.
(4) Riscaldamento (EN 14511 e EN 14825) temperatura aria ambiente 20 °C b.s.; temperatura aria esterna 7 °C b.s. / 6 °C b.u.; velocità turbo; lunghezza linee frigorifere 5 m.
(5) La potenza nominale assorbita (corrente nominale assorbita), è la massima potenza elettrica assorbita (corrente massima assorbita) dal sistema, in accordo con la normativa EN 60335-1 e EN 60335-2-40.
(6) Pressione sonora misurata in camera anecoica a 1,5 m di distanza frontale.
40