Page 396 - AERMEC - CATALOGO PRODOTTI 2024 - FIDRA
P. 396

INDICI ENERGETICI (REG. 2016/2281 UE)
                 Taglia                            021   026   031   041  050   070   080   090   102   152   202
                 SEER - 12/7 (EN14825: 2018) con ventilatori standard (1)
                                       °     W/W   - (2)  - (2)  - (2)  - (2)  - (2)  - (2)  - (2)  - (2)  - (2)  - (2)  - (2)
                                       A,P   W/W   4,18  4,20  4,17  4,10  4,16  4,34  4,19  4,31  4,11  4,11  4,10
                 SEER
                                       N     W/W    -     -    -     -     -     -     -     -    - (2)  - (2)  - (2)
                                       Q     W/W    -     -    -     -    - (2)  - (2)  - (2)  - (2)  - (2)  - (2)  - (2)
                                       °      %    - (2)  - (2)  - (2)  - (2)  - (2)  - (2)  - (2)  - (2)  - (2)  - (2)  - (2)
                                       A,P    %   164,00  164,80  163,60  161,00  163,40  170,70  164,60  169,40  161,30  161,20  161,10
                 Efficienza stagionale
                                       N      %     -     -    -     -     -     -     -     -    - (2)  - (2)  - (2)
                                       Q      %     -     -    -     -    - (2)  - (2)  - (2)  - (2)  - (2)  - (2)  - (2)
                 SEER - 23/18 (EN14825: 2018) con ventilatori standard (3)
                                       °     W/W   4,34  4,35  4,31  4,21  4,55  4,68  4,49  4,61  4,83  4,73  4,69
                                       A,P   W/W   4,49  4,51  4,48  4,47  4,55  4,64  4,57  4,66  4,49  4,25  4,28
                 SEER
                                       N     W/W    -     -    -     -     -     -     -     -    4,15  4,18  4,23
                                       Q     W/W    -     -    -     -    4,18  4,44  4,35  4,49  4,15  4,18  4,23
                                       °      %   170,40  170,90  169,20  165,20  179,10  184,30  176,60  181,50  190,30  186,00  184,70
                                       A,P    %   176,70  177,50  176,00  175,60  179,00  182,40  179,80  183,50  176,60  167,00  168,00
                 Efficienza stagionale
                                       N      %     -     -    -     -     -     -     -     -   163,10  164,20  166,00
                                       Q      %     -     -    -     -    164,30  174,50  171,10  176,70  163,10  164,20  166,00    ARIA-ACQUA
                 SEPR - (EN 14825: 2018) Alta temperatura con ventilatori standard (3)
                                       °     W/W   5,92  5,92  5,85  5,69  6,36  6,50  6,21  6,43  6,79  6,58  6,49
                                       A,P   W/W   6,56  6,57  6,45  6,21  6,74  6,90  6,55  6,78  6,68  6,18  6,17
                 SEPR
                                       N     W/W    -     -    -     -     -     -     -     -    5,91  6,09  6,10
                                       Q     W/W    -     -    -     -    6,03  6,28  6,08  6,30  5,91  6,09  6,10
                 (1)  Calcolo eseguito con portata d’acqua FISSA e temperatura d’uscita VARIABILE.
                 (2)  Non conformi al regolamento 2016/2281 UE per applicazioni di comfort 12°C / 7°C
                 (3)  Calcolo eseguito con portata d’acqua FISSA.

                 DATI ELETTRICI
                 Taglia                            021   026   031   041  050   070   080   090   102   152   202
                 Alimentazione: °
                 Dati elettrici
                                       °      A    5,0   6,0   6,0   9,0  11,0  14,0  16,0  17,0  22,0  26,0  32,0
                                       A,P    A    6,0   7,0   7,0   10,0  13,0  15,0  18,0  19,0  23,0  28,0  34,0
                 Corrente massima (FLA)
                                       N      A     -     -    -     -     -     -     -     -    24,0  28,0  34,0
                                       Q      A     -     -    -     -    12,0  14,0  17,0  18,0  24,0  28,0  34,0
                                       °      A    28,0  38,0  39,0  44,0  65,0  75,0  102,0  96,0  76,0  87,0  117,0
                                       A,P    A    29,0  39,0  40,0  45,0  67,0  77,0  104,0  98,0  77,0  89,0  119,0
                 Corrente di spunto (LRA)
                                       N      A     -     -    -     -     -     -     -     -    78,0  89,0  119,0
                                       Q      A     -     -    -     -    66,0  76,0  103,0  97,0  78,0  89,0  119,0
                 Taglia                            021   026   031   041  050   070   080   090   102   152   202
                 Alimentazione: M
                 Dati elettrici
                                       °      A    13,0  16,0  18,0  22,0  -     -     -     -     -    -     -
                 Corrente massima (FLA)  A,P  A    14,0  17,0  19,0  23,0  -     -     -     -     -    -     -
                                       N,Q    A     -     -    -     -     -     -     -     -     -    -     -
                                       °      A    64,0  68,0  69,0  100,0  -    -     -     -     -    -     -
                 Corrente di spunto (LRA)  A,P  A  62,0  69,0  70,0  101,0  -    -     -     -     -    -     -
                                       N,Q    A     -     -    -     -     -     -     -     -     -    -     -

                 DATI TECNICI GENERALI
                                                  ANL021  ANL026  ANL031  ANL041  ANL050  ANL070  ANL080  ANL090  ANL102  ANL152  ANL202
                 Compressore
                 Tipo                       tipo                                Scroll
                 Regolazione compressore    Tipo                                On-Off
                 Numero                     n°     1     1     1     1     1     1     1    1     2     2     2
                 Circuiti                   n°     1     1     1     1     1     1     1    1     1     1     1
                 Refrigerante               tipo                                R410A
                 Carica refrigerante (1)    kg     1,2   1,2   1,2  1,3   2,8   2,8   3,0   3,9   5,9   5,9   5,9
                 Scambiatore lato utenza
                 Tipo                       tipo                               Piastre
                 Numero                     n°     1     1     1     1     1     1     1    1     1     1     1
                 Attacchi idraulici lato utenza
                 Diametro (in/out)          Ø                                   1”1/4
                 Ventilatore
                 Tipo                       tipo                               Assiale
                 Motore ventilatore         tipo                           Asincrono con taglio di fase
                 Numero                     n°     1     1     1     1     1     1     1    1     2     2     2
                 Portata aria               m³/h  2500  2500  3500  3500  7200  7200  7300  7200  14000  13500  13500
                 Dati sonori calcolati in funzionamento a freddo (2)


             394                                            www.aermec.com                        ANL-021-202-CO_I_CE50_04
   391   392   393   394   395   396   397   398   399   400   401